Technical Informations / Clamp Interspaces

Fixed clamp interspaces are provided in the side table for composite pipes placed horizontally.  Clamp interspaces in the vertical piping system must be same with the clamp interspaces in the horizontal piping system.

Fixed Points:  Fixed points prevent the movements uncontrollable in the system and in addition separates all system into small expansion sections.  The places of the fixed points are identified by taking into account stretching amount, weight, type of liquid inside of the pipe and other forces, if any.  

Fixed points must be more robust than the pushing force of the free bending part.  Fixed points must be placed in proper distances so as to enable expansion.

Fixed points are used to fasten pipes firmly on a place.  Fixed points make use of the muff and fitting weld places in the terminals or double side fixing systems. 

Temperature Difference AT  (ºC) Pipe Diameter                
  Ø 20 mm Ø 25 mm Ø 32 mm Ø 40 mm Ø 50 mm Ø 63 mm Ø 75 mm Ø 90 mm Ø 110 mm
0ºC 115 130 150 165 185 215 240 260 280
20ºC 90 100 115 130 145 165 185 200 215
30ºC 90 100 115 130 145 165 185 200 210
40ºC 80 90 105 120 135 155 175 190 200
50ºC 80 90 105 120 135 155 175 190 180
60ºC 70 80 100 115 130 145 165 180 175
70ºC 65 75 90 105 120 135 155 175 175